Detaljer

  • Design features SQV: Torque range from 150 Nm to 2,400 Nm Swing angle from 75° to 105° Operating times for 90° from 4 s to 360 s Limit and torque sensing Mains connection: 1-phase and 3-phase Handwheel for manual operation Mechanical position indicator
  • Design features SQRV: Torque range from 150 Nm to 2,400 Nm Modulating torque range from 52 Nm to 840 Nm Max. number of starts 1,500 c/h Swing angle from 75° to 105° Operating times for 90° from 4 s to 360 s Limit and torque sensing Mains connection: 1-phase and 3-phase Handwheel for manual operation Mechanical position indicator
  • Ambient conditions: High enclosure protection High quality corrosion protection Wide ambient temperature ranges
  • Interfaces: Electrical connection via AUMA plug/socket connector (terminals as an option) Cable entries in different versions Output drive types according to DIN and EN ISO standards
  • Interface and functional properties: Programmable, potential-free output contacts for status signalling Soft start and stop for gentle valve operation Avoiding pressure surge by an operating time profile EMERGENCY behaviour and safety behaviour with separate operating time setpoints Process controller (PID) Fieldbus control Behaviour in case of emergency situations and communication loss (programmable) Operation data logging Bluetooth interface to notebook and Android tablet.
  • Options: Intermediate position switches Switches in tandem version Remote position transmitter Magnetic limit and torque transmitter

Variable operating time actuators SQV and SQRV

With SQV .2 part-turn actuators for open-close duty and SQRV .2 for modulating duty paired with ACV .2 actuator controls, the proven AUMA SQ/SQR range is enhanced by variable operating time models.

AUMA is spearheading market technology, offering a wide operating time range with a ratio of up to 1:10.

Actuators of the SQV type range are rated for open-close duty and positioning duty (classes A and B) / (short-time duty S2 - 15 min).

Actuators of the SQRV type range are rated for modulating duty (class C) S4 - 25 %.