Ambient conditions: 
  • High enclosure protection
  • High quality corrosion protection
  • Wide ambient temperature ranges
Interfaces: 
  • Electrical connection via AUMA plug/socket connector (terminals as an option)
  • Cable entries in different versions
  • Output drive types according to DIN and EN ISO standards
Interface and functional properties:
  •  Programmable, potential-free output contacts for status signalling
  • Soft start and stop for gentle valve operation
  • Avoiding pressure surge by an operating time profile
  • EMERGENCY behaviour and safety behaviour with separate operating time setpoints
  • Process controller (PID)
  • Fieldbus control
  • Behaviour in case of emergency situations and communication loss (programmable)
  • Operation data logging Bluetooth interface to notebook and Android tablet.
Options:
  • Intermediate position switches Switches in tandem version Remote position transmitter Magnetic limit and torque transmitter

Variable operating time actuators SQV and SQRV

With SQV .2 part-turn actuators for open-close duty and SQRV .2 for modulating duty paired with ACV .2 actuator controls, the proven AUMA SQ/SQR range is enhanced by variable operating time models.

AUMA is spearheading market technology, offering a wide operating time range with a ratio of up to 1:10. Actuators of the SQV type range are rated for open-close duty and positioning duty (classes A and B) / (short-time duty S2 - 15 min). Actuators of the SQRV type range are rated for modulating duty (class C) S4 - 25 %.

Design features SQV: 
  • Torque range from 150 Nm to 2,400 Nm
  • Swing angle from 75° to 105°
  • Operating times for 90° from 4 s to 360 s
  • Limit and torque sensing
  • Mains connection: 1-phase and 3-phase
  • Handwheel for manual operation
  • Mechanical position indicator
Design features SQRV: 
  • Torque range from 150 Nm to 2,400 Nm
  • Modulating torque range from 52 Nm to 840 Nm
  • Max. number of starts 1,500 c/h
  • Swing angle from 75° to 105°
  • Operating times for 90° from 4 s to 360 s
  • Limit and torque sensing
  • Mains connection: 1-phase and 3-phase
  • Handwheel for manual operation
  • Mechanical position indicator
Learn more about: 